VTX-WM1 Installation Guide v1.212
Event Log and log conguration
A log is maintained for the amplier. The
log records power-on and power-off, over-
temperature, impedance test pass/fail and email
alert failures, all against the on-board clock/
calendar. The Event logging pane on the Site
Conguration page lets you dene which of
these events are to be recorded and whether
any (or all) of them should generate email
alerts.
For each of the six event types, one of the
following options may be set:
• None – events of this type are ignored
• Log only – events of this type are
recorded in the log
• Log & email – events are recorded in
the log and also entered in an alert email,
but the email is not sent at this time.
• Email Trigger – events are recorded
in the log, and the alert email is sent; this
will contain the current event and any
events recorded via the Log & email
option above.
The Event log for the amplier may be
inspected by clicking on the amplier’s button
(opens the Amplier Properties page),
and then clicking on Event Log below the
button.
Impedance Tests
The VTX-WM1 card includes a variable
frequency test oscillator which may be
programmed to apply a test tone (at 40 dB
below the amplier’s maximum output level) to
the amplier output at a future date and time,
and, if desired, at regular intervals thereafter.
(It is recommended that tests are scheduled
for the hours of building non-occupation).
The amplier output voltage and current are
monitored during the test and hence the load
impedance checked. This gives the engineer
a rst-line conrmation that all the speakers
connected to each amplier channel are
present, connected and functional.
Clicking Tests (click the amplier button
rst) opens the Test List page for the
amplier:
In order for the impedance tests to be
meaningful, an initial Load Conguration